Shopping Cart is Temporarily Down. Please Call for Pricing!

Protectorelay Oil Burner Relay with Lock Out Timing

Call for Pricing
- +
In stock
1 Available At My Branch
10 Available At All US Supply Locations

Brand
Honeywell
Part Number
R8184G4009/U
SKU
1691
Manufacturer
Honeywell

Details

Honeywell Protectorelay Oil Burner Control, 120 to 240 VAC, 3.7 to 7.4 A, Intermittent Ignition, -40 to 130 degree Fahrenheit, Junction Box Mount, 4-3/8 inch height x 4 1/8 inch Width x 2 1/2 inch D

The TRADELINE intermittent ignition oil primary control operates the oil burner, oil valve (if desired) and the ignition transformer inch response to a call for heat from the thermostat. Through a C554 Cad Cell Flame Sensor, the R8184 monitors the burner flame and shuts down the system on ignition failure or on flame failure during the run cycle. A light emitting diode (LED) on the terminal strip lights when the safety switch opens to provide safety shutdown indication. A manual reset button is provided to reset the safety switch after lockout. For convenience inch system maintenance, the safety switch can be manually opened using a lever on the front of the control. Clock thermostats that power the clock through the primary control transformer will lose time during lockout unless backup batteries are installed.

Specifications

Specifications
SKU1691
Weight1.250000
Control TypeIgnition Controls
Mounting TypeJunction Box
Ignition TypeIntermittent
Humidity Control0
Item ReturnsThis item can be returned
Features

Features

  • Amperage Rating: 3.7 to 7.4 A
  • Temperature Rating: -40 to 130 deg F
  • Primary Voltage: 120 to 240 VAC
  • Warranty: Limited
  • Height: 4-3/8 in
  • Width: 4 1/8 in
  • Depth: 2 1/2 in
  • Domestic/Import: Domestic
  • Provides automatic, no recycling control of an intermittent ignition oil burner system
  • 22.2 to 44.4 A at 120 to 240 VAC for locked rotor
  • Controls oil burner, oil valves (if desired) and the ignition transformer in response to a call for heat
  • Solid state flame sensing circuit
  • LED on terminal strip indicates system lockout
  • Remote lockout indication
  • Enclosed safety switch with external reset button
  • Manual trip lever opens safety switch for system maintenance
  • Mounts on standard 4 x 4 in junction box select models may be mounted directly on burner housing
  • C554A cadmium sulfide flame detector and 24 VAC thermostat required